Indirect Control of a low power Single-Phase Active Power Filter

  • Silviu Epure “Dunarea de Jos” University of Galati
  • Emil Roșu “Dunarea de Jos” University of Galati
Keywords: active power filtering, indirect control, PWM rectifier, THD

Abstract

This paper deals with a low power, single phase active filter used to compensate nonlinear loads. The filter uses the indirect control method and it is based on a particular connection between filter, polluting load and grid to avoid time-consuming mathematic operations or signal processing computations and assures good rejection of harmonic currents injected by the nonlinear load into the grid. A scale model was first simulated in Simulink and then physically implemented. The paper presents simulation and experimental results, and highlight problems encountered during experiments.

Published
2010-12-05
How to Cite
1.
Epure S, Roșu E. Indirect Control of a low power Single-Phase Active Power Filter. The Annals of “Dunarea de Jos“ University of Galati. Fascicle III, Electrotechnics, Electronics, Automatic Control, Informatics [Internet]. 5Dec.2010 [cited 5May2024];33(2):27-4. Available from: https://www.gup.ugal.ro/ugaljournals/index.php/eeaci/article/view/606